Transportation Center
Staff Input per Category
- Functionality/Efficiency/Flexibility:
Need more maintenance bays, better storage, paint booth, limited space in
general
- Collaboration/Connections: Need
training room and lot
- Accessibility/Special Programming: None
- Comfort & Well Being: Ventilation
upgrades
- Safety & Security: Automatic bus
wash, unsecured site, parking, traffic & pedestrian circulation and
control, gas tank location, vandalism, tool storage & protection, need
dedicated entrance
Conditional Assessment (Overall Suitability: 59%)
Conditional Assessment Summary of Needs
- Site: Items that scored poorly include size of
site, access and traffic flow (safety concerns), overall drainage, main
building sign, site directional signage, site perimeter fencing, dumpster area,
mechanical courtyard, drives and lots asphalt and walks, fuel island asphalt,
soccer field and softball fields and buildings generally scored low overall.
- Architectural: A pre-engineered metal building
with CMU uninsulated walls with a small residential type construction office
attached. The metal siding is damaged
along the base and asphalt has been poured up to the panels. Roof appears to be in good condition. Windows at the office are vinyl residential
type. Overhead garage doors are in good
condition. One CMU wall at the stair is
not stable and moves when pushed against.
- Interiors: The maintenance
portion of this building looks very nice finish-wise. The flooring consists of
epoxy resin, CPT, and VCT – all appear to be in great shape still. Furniture in
this appear new in offices. There is a section of the wall by a stairwell that needs
to be addressed as it moves when pushed. The adjacent connecting offices appear
to have the updated CPT. Furnishings are a mix of ages/styles/finishes. Only
some windows have horizontal blinds that could be switched out with roller
shades.
- Mechanical: The ground-mounted rooftop unit that serves
the main space is in new condition. The upper and lower support spaces are
conditioned by three other ground-mounted rooftop units that are in poor
condition and should be replaced. The wall heaters, prop unit heaters and
inline exhaust fans are all in poor condition and should be replaced. HVLS fans
are in good condition. The office is served by a split system furnace in fair
condition.
- HVAC Controls: Distech Controls - Connected to all (4) ground mounted DX/Gas Rooftop Unit. No immediate needs for controls upgrades
- Electrical: No generator is
available, apparently one is required per director; (2) electrical services
(1974) both in poor condition, should be replaced; fire alarm system installed
in 2021 in excellent condition; interior lighting is mostly LED, with flat
panels, retrofit tubes and high-bays; mostly manual controls, except where
remodels have occurred, occupancy sensors are in those same locations; exterior
lighting LED bus parking lot and LED and HID on building; exterior lighting has
BMS controls
- Plumbing: The water service
entrance and domestic water piping are in poor condition and should be
replaced. The domestic water service entrance does not include a domestic water
backflow preventer. A backflow preventer needs to be installed to protect the
city main from the school during a backflow event. The plumbing fixtures are in
fair to good condition. The gas piping appears to be I good condition.
- Technology:
- No electronic door monitoring. Staff walk around
building at day’s end to check doors.
- Video surveillance. A lot of blind spots around the exterior
of the buildings.
- Classroom A/V. In working condition but getting dated.
They are planning projects to update.